Steel tapescreen xlpe insulation controlcable
Structure:
1.Stranded copper conductor for single or shaped conductor for multi-corecables
2.PVC insulated
3.PVC bedding,zinc plating steel wire armored
4.PVC sheathed cables
Standard: IEC60502
Application:
used in laying outdoors underground,be able to bear external mechanicalforces
Voltage:0.6/1kv
package:regular export carton package or as customer'srequest
Min. order quantity:1000meters
Attached table:
Item No. | Core No. | insulation thinckness | jacket thinckness | Max. outside diameter | Min. outside diameter |
KVV22-No1 | 14x4 | 0.8 | 1.7 | 22.0 | 26.5 |
KVV22-No2 | 14x6 | 0.8 | 1.7 | 24.0 | 29.0 |
KVV22-No3 | 16x0.75 | 0.6 | 1.5 | 15.0 | 19.5 |
KVV22-No4 | 16x1.0 | 0.6 | 1.5 | 16.0 | 20.0 |
KVV22-No5 | 16x1.5 | 0.7 | 1.7 | 18.0 | 22.5 |
KVV22-No6 | 16x2.5 | 0.8 | 1.7 | 21.0 | 25.5 |
KVV22-No7 | 19x0.75 | 0.6 | 1.5 | 15.5 | 20.0 |
KVV22-No8 | 19x1.0 | 0.6 | 1.7 | 17.0 | 21.5 |
KVV22-No9 | 19x1.5 | 0.7 | 1.7 | 19.0 | 23.5 |
KVV22-No10 | 19x2.5 | 0.8 | 1.7 | 22.0 | 26.5 |
KVV22-No11 | 24x0.75 | 0.6 | 1.7 | 18.0 | 22.5 |
KVV22-No12 | 24x1.0 | 0.6 | 1.7 | 19.0 | 23.5 |
KVV22-No13 | 24x1.5 | 0.7 | 1.7 | 21.5 | 26.5 |
KVV22-No14 | 24x2.5 | 0.6 | 1.7 | 25.0 | 30.0 |
KVV22-No15 | 27x0.75 | 0.6 | 1.7 | 18.5 | 23.0 |
KVV22-No16 | 27x1.0 | 0.6 | 1.7 | 19.5 | 24.0 |
KVV22-No17 | 27x1.5 | 0.7 | 1.7 | 22.0 | 27.0 |
KVV22-No18 | 27x2.5 | 0.8 | 1.7 | 25.5 | 30.5 |
KVV22-No19 | 30x0.75 | 0.6 | 1.7 | 19.0 | 23.5 |
KVV22-No20 | 30x1.0 | 0.6 | 1.7 | 20.0 | 24.5 |
KVV22-No21 | 30x1.5 | 0.7 | 1.7 | 23.0 | 27.5 |
KVV22-No22 | 30x2.5 | 0.8 | 1.7 | 26.5 | 31.5 |
Operating Characteristics
Rated voltage: 0.6/1(1.2)kV
Max. permissible continuous operating temperature of conductor: 70°C
Max. temperature of conductor during short-circuit (5s max. duration) shall not exceed:
Nominal cross section of conductor ≤300mm2: 160 °C
Nominal cross section of conductor >300mm2: 140 °C
The ambient temperature under installation should not be lower than: 0 °C
The bending radius of cable is recommended as following:
For single core cable: not less than 15 times of the diameter of cable
For
multi-core cable: not less than 12 times of the diameter of cable
When the armoured single core cable used for Alternative Current(AC) system, the armour material should be non-magnetic.
Application
TheSteel tape screen xlpe insulation
control cable is used for fixed installations such as electric power distribution networks or industrial installations, which is laid indoors, in tunnel, in cable trench or direct in ground, able to bear external mechanical force, but unable to bear large pulling force.
Manufacturing Standards
GB/T 12706-2008, IEC 60502-1